Connection Diagram of AC Control SSR

This is an Application note i used to give with my ssr - app011.pdf -
SSR or Solid State Relay or Electronic Relay
This is a Thyristor Based Normally Open 230V Switch that can be turned on / off at a fast rate. This switches at Zero Crossover .Built In Snubber reduces EMI and protects the SSR. USE SAME PHASE FOR I/P & O/P.
AC-AC SSR Wiring
  • No moving parts hence no wear and tear.
  • Dissipates Heat when in On Condition.
  • Use adequate Heat Sink or SSR will fail. ( 10g / Amp)
  • Dissipation is 1.5 Watts per Amp thru Load.
  • Input to Output is optically isolated 2kV.
  • This one is AC 230V Control AC 230V N.O. Output.
  • Off state snubber Leakage is around 5 mA.
Notes -
The Termination's of High Current Lines going to Load must be very tight and crimped. Loose contacts will Spark and cause Fire.
Fuse Rating of HRC Fuse - High Rupture Capacity (HRC) Fuse is Safe and Reliable. 5kW Heater at 230V is 5,000 / 230 in Amps of Fuse Rating.